Algorithmic Center of 1 Loop – AE/SA-C1 Aguilera Electronica
Algorithmic Analog Microprocessor Central, manufactured by AGUILERA ELECTRÓNICA according to European standards UNE-EN 54-2 y ONE 54-4,
with wide operating capacity that allows you to individually control all the equipment that makes up the fire detection facilities.
Intelligent fire control panel with capacity for 1 loops of 125 teams, to which the detectors are connected, pushbuttons, maneuvering modules, control and other elements that configure the installation.
Allows the connection of CLASS A loops: closed loop with independent input and output isolators; and CLASS B loops: open loop with output isolator.
Switch mode power supply 27.2 Vcc 4 A, planned to meet the needs of the plant and the installation.
Emergency battery charger. The control unit has the capacity to house two 12V batteries inside. / 7 Ah.
Módulo CPU, where the installation is customized, departure maneuvers are programmed and information is managed. Its main features are:
Non-volatile event memory, with capacity for 4000 events. Real time clock.
Complete control of the operation of all the equipment that make up the installation on a scheduled or manual basis:
rearms, reruns, levels, connecting / disconnecting points, activation / deactivation of evacuations, closing fire doors and dampers.
Programming of delays according to standard UNE EN54-2.
DAY / NIGHT modes automatically configurable by programmable calendar.
Fire brigade warning output with programmable activation times: Recognition time and investigation time, according to NEN2535 standard.
Built-in test and test modes for each zone.
Supports several working languages.
Comprehensive management of historical lists between two dates and status of the zones.
240 graphic display×64 points. Control keyboard.
Indicator lights and local buzzer, for presentation of general service statuses, alarm, fault, disconnection, test, power supply and status of evacuation maneuvers and other.
Additional information
Weight | 10 kg |
---|---|